What
does a Landlord Gas Safety Inspection Include?
1. Check appliance for gas tightness.
2. Check standing and working pressure if test points available.
3. Check burner pressure / gas rate against manufacturers data
plate.
4. Check for satisfactory provision of all necessary ventilation.
5. Test flue flow to ensure removal of products of combustion.
6. Check satisfactory operation of all the flame failure devices.
7. Check for physical stability, presence and effectiveness
of stability brackets
(where appropriate).
8. Investigate any evidence of unsafe operation and report to
a responsible
person. An
appliance can
not be deemed
as having been checked, until the
above has been completed.
9. For a Landlords Safety Record inspection a tightness test of
the
full system
should be added
to the
above.
Boiler
Servicing & Repairs
Central Heating Design & Installation
Power Flushing
Under Floor Heating
Solar Power Hot Water |